【免费使用】点击查看详情
来源网络
设备 Equipment |
周期 Interval |
检查要求 Outline of Requirement |
规则出处 Guideline |
手提灭火器 Portable fire extinguishers |
Annually |
Inspections in accordance with the manufacturer’s instructions, etc. |
Res.A.951(23), para.9.1 |
5-yearly |
Discharged as part of fire drills, etc. |
Res.A.951(23), para.9.1.1 |
|
10-yearly |
Hydrostatic test |
Res.A.951(23), para.9.1.2 |
|
舟车式灭火器 Wheeled (mobile) fire extinguishers |
Monthly |
Verification in place, etc. |
MSC.1/Circ.1432, para.5.9 |
Annually |
Inspections in accordance with manufacturer’s instructions, etc. |
MSC.1/Circ.1432, para.7.12 |
|
5-yearly |
Visual inspection, etc. |
MSC.1/Circ.1432, para.9.6 |
|
10-yearly |
Hydrostatic test |
MSC.1/Circ.1432, para.10.5 |
|
手提泡沫喷射器 Portable foam applicator units |
Monthly |
Inspections in accordance with manufacturer’s instructions, etc. |
MSC.1/Circ.1432, para.5.8 |
Annually |
foam control test, etc. |
MSC.1/Circ.1432, para.7.11 |
|
固定二氧化碳系统 Fixed CO2 fire-extinguishing systems |
Monthly |
Verification of each part, etc. |
MSC.1/Circ.1318, para.4 |
Annually |
Visual inspection, etc. |
MSC.1/Circ.1318, para.5 |
|
2.5-yearly |
Verification of contents, etc. |
MSC.1/Circ.1318, para.6.1 |
|
5-yearly |
Operation test, etc. |
MSC.1/Circ.1318, para.6.2 |
|
10-yearly |
Hydrostatic test, etc. |
MSC.1/Circ.1318, para.6.1 |
|
固定干粉系统 Fixed dry chemical powder systems |
Monthly |
Verification of valves and gauges, etc. |
MSC.1/Circ.1432, para.5.6 |
Annually |
Visual inspection, etc. |
MSC.1/Circ.1432, para.7.9 |
|
2-yearly |
Testing a sample of dry chemical powder, etc. |
MSC.1/Circ.1432, para.8.2 |
|
10-yearly |
Hydrostatic test or Non-destructive test |
MSC.1/Circ.1432, para.10.3 |
|
固定泡沫系统 Fixed foam fire-extinguishing systems |
Monthly |
Verification of valves and gauges, etc. |
MSC.1/Circ.1432, para.5.3 |
Quarterly |
Verification of quantity of foam concentrate |
MSC.1/Circ.1432, para.6.2 |
|
Annually |
Functional test, and taking sample, etc. |
MSC.1/Circ.1432, para.7.4 |
|
5-yearly |
Inspection of each part |
MSC.1/Circ.1432, para.9.2 |
|
呼吸器 SCBAs |
Weekly |
Examination of cylinder gauges |
MSC.1/Circ.1432, para.4.5 |
Annually |
Checking of serviceable condition, etc. |
MSC.1/Circ.1432, para.7.8.2 |
|
5-yearly |
Hydrostatic test |
MSC.1/Circ.1432, para.9.4 |
|
紧急逃生呼吸器 EEBD |
Weekly |
Examination of cylinder gauges |
MSC.1/Circ.1432, para.4.5 |
Annually |
Inspections in accordance with manufacturer’s instructions, etc. |
MSC.1/Circ.1432, para.7.8.3 |
|
--- |
Hydrostatic test |
IACS Rec.88 |
|
水喷淋系统 Water mist, water spray and sprinkler systems |
Weekly |
Visual inspection, etc. |
MSC.1/Circ.1432, para.4.7 |
Monthly |
Verification of valves and gauges, etc. |
MSC.1/Circ.1432, para.5.4 |
|
Quarterly |
Assessment of system water quality |
MSC.1/Circ.1516, para 6.5 |
|
Annually |
Blowing air, blowing water test, etc. |
MSC.1/Circ.1516, para 7.5 |
|
5-yearly |
Internal inspection of all control/section valves, etc. |
MSC.1/Circ.1516, para 9.3 |
|
10-yearly |
Hydrostatic test for gas and water pressure cylinders. |
MSC.1/Circ.1432, para.10.2 |
欢迎大家补充